Introducing our superior 20kV oil-immersed transformer, a pinnacle of electrical innovation! This essential piece of equipment relies on premium insulating oil to effectively serve as the insulating medium. Comprising an advanced iron core, precision-engineered coil, a robust voltage-regulating switch, and a fortified oil tank, this transformer excels in modifying voltage and transmitting alternating current with remarkable efficiency. Notable for its compact design, budget-friendly pricing, and exceptional resistance to harsh weather conditions, it is the top choice across diverse sectors such as power systems, industrial and mining enterprises, transportation, postal and telecommunications, and renowned scientific research institutions.
nominal
capacity
|
high
voltage side
|
High voltage
tap range
|
low
voltage side
|
Connection
group labeling
|
No-
load loss
|
Load Loss |
No-load
current
|
Short Circuit
Impedance
|
30KVA |
11KV
10.5KV
10KV 6.3KV 6KV |
±5
±2×2.5%
|
0.4KV
0.69KV
|
Dyn11
Yyn0
|
100W | 630/600W | 2.3% | 4% |
50KVA | 130W | 910/870W | 2.0% | 4% | ||||
63KVA | 150W | 1090/1040W | 1.9% | 4% | ||||
80KVA | 180W | 1310/1250W | 1.9% | 4% | ||||
100KVA | 200W | 1580/1500W | 1.8% | 4% | ||||
125KVA | 240W | 1890/1800W | 1.7% | 4% | ||||
160KVA | 280W | 2310/2200W | 1.6% | 4% | ||||
200KVA | 340W | 2730/2600W | 1.5% | 4% | ||||
250KVA | 400W | 3200/3050W | 1.4% | 4% | ||||
315KVA | 480W | 3830/3650W | 1.4% | 4% | ||||
400KVA | 570W | 4520/4300W | 1.3% | 4% | ||||
500KVA | 680W | 5410/5150W | 1.2% | 4% | ||||
630KVA | 810W | 6200W | 1.1% | 4.5% | ||||
800KVA | 960W | 7500W | 1.0% | 4.5% | ||||
1000KVA | 1150W | 10300W | 1.0% | 4.5% | ||||
1250KVA | 1360W | 12000W | 0.9% | 4.5% | ||||
1600KVA | 1640W | 14500W | 0.8% | 4.5% | ||||
2000KVA | 1960W | 19800W | 0.8% | 5% | ||||
2500KVA | 2310W | 23000W | 0.7% | 5% |
Installation Instructions:
1. Installation form:
Our versatile 20kV oil-immersed transformers offer multiple installation options including pole-mounted, outdoor, and indoor transformer setups, allowing you to choose the perfect fit for your needs.
For outdoor installations, secure the transformer on a reinforced concrete foundation. For indoor setups, ensure the transformer aligns with the cabinet's front, snugly fitting against the distribution panel with no gaps for optimum performance.
2. Installation steps:
Ensure the transformer is properly positioned using specifically designed force points, accompanied by effective anti-slip measures to guarantee stability.
During transportation and installation, maintain the transformer's body inclination within safe limits-no more than 15° along the long axis and 10° along the short axis.
Pay close attention to component gaps during installation to avoid any issues from overly tight or loose fittings.
Select the appropriate insulation disks tailored to the situation for terminal installation, ensuring correct wiring for optimal performance.
3. Attachment installation:
When fitting accessories such as gas relays, pressure relief devices, moisture absorbers, and sleeves, all standards and manufacturer guidelines must be strictly followed to ensure safety and reliability.
Certificates: