Epoxy Resin Dry-Type Transformer
Safe, Efficient, Environmentally Friendly, and Energy-Saving Power Solutions
parameter term |
parameter values |
rated voltage |
Various specifications available, such as 20KV, 10KV, 6KV, etc. |
Capacity range |
Various specifications are available, such as 500KVA, 630KVA, 800KVA, 1250KVA, etc. |
Cooling Method |
Natural air-cooled/forced air-cooled (according to specific models) |
Insulation material |
Epoxy resin or other high-performance insulating materials |
Protection class |
IPXX (according to the specific model, need to mark the specific level) |
Winding type |
Foil winding structure (low voltage) / "trapezoidal" segmented layer structure (high voltage) |
Core material |
High quality cold rolled grain oriented silicon steel sheet |
Technical Data Sheet for 6KV, 10KV Class 10 Dry Type Non-Excited Regulated Distribution Transformer |
nominal capacity |
Connection
group labeling
|
Voltage combination |
No-load
current
|
No-
load loss
|
Load Losses at Different Insulation Thermal Ratings |
Short Circuit
Impedance
|
B(100ºC) |
F(120ºC) |
H(145ºC) |
30KVA |
Yyn0
Dyn11 |
6-11±2×2.5%/0.4 |
2.1 |
190 |
670 |
710 |
760 |
4.0 |
50KVA |
2.1 |
270 |
940 |
1000 |
1070 |
4.0 |
80KVA |
1.6 |
370 |
1290 |
1380 |
1480 |
4.0 |
100KVA |
1.6 |
400 |
1480 |
1570 |
1690 |
4.0 |
125KVA |
1.5 |
470 |
1740 |
1850 |
1980 |
4.0 |
160KVA |
1.5 |
540 |
2000 |
2130 |
2280 |
4.0 |
200KVA |
1.3 |
620 |
2370 |
2530 |
2710 |
4.0 |
250KVA |
1.3 |
720 |
2590 |
2760 |
2960 |
4.0 |
315KVA |
1.1 |
880 |
3270 |
3470 |
3730 |
4.0 |
400KVA |
1.1 |
980 |
3750 |
3990 |
4280 |
4.0 |
500KVA |
1.1 |
1160 |
4590 |
4880 |
5230 |
4.0 |
630KVA |
0.9 |
1340 |
5530 |
5880 |
6290 |
4.0 |
630KVA |
0.9 |
1300 |
5610 |
5960 |
6400 |
6.0 |
800KVA |
0.9 |
1520 |
6550 |
6960 |
7460 |
6.0 |
1000KVA |
0.9 |
1770 |
7650 |
8130 |
8760 |
6.0 |
1250KVA |
0.9 |
2090 |
9100 |
9690 |
10370 |
6.0 |
1600KVA |
0.9 |
2450 |
11050 |
11730 |
12580 |
6.0 |
2000KVA |
0.9 |
3050 |
13600 |
14450 |
15560 |
6.0 |
2500KVA |
0.7 |
3600 |
16150 |
17170 |
18450 |
6.0 |
Basic Structure of Dry-Type Transformer
1. Iron Core: Composed of silicon steel sheets, the iron core forms the magnetic circuit of the transformer, guiding magnetic flux with precision.
2. Winding: Comprising high-voltage and low-voltage windings, these components encircle the iron core to facilitate the transformation and transmission of electrical energy.
3. Insulating Cylinder: Positioned between high and low voltage coils, this ensures robust electrical insulation, safeguarding the transformer's operation.
4. Pads: Designed to support and maintain the integrity of the coils, ensuring stability and preserving their form.
5. Fasteners: Essential for securing and interconnecting each segment of the transformer, equipped with anti-loosening capabilities.
Product Description:
Overview:
The 10kV Dry-Type Transformer, featuring a core and windings unimmersed in insulating liquid, offers safety, fire resistance, and pollution-free operation. It's an ideal choice for power systems in industrial, commercial, and civil domains.
Main Features:
Superior Safety Performance: Fireproof and pollution-free, this transformer can be installed directly at load centers, enhancing system security.
High Mechanical Strength: Exhibiting robust short-circuit resistance, minimal partial discharge, and excellent thermal stability, it ensures a long lifespan.
Remarkable Energy-Saving Effect: With low loss and noise, high operational efficiency, it meets modern energy-saving and environmental protection standards.
Excellent Heat Dissipation Performance: Boasting superior heat dissipation and operational capabilities, forced air-cooling enhances its functional capacity.
Strong Environmental Adaptability: Exceptional moisture resistance allows operation in high humidity and challenging environments.
Low Maintenance Cost: Environmentally friendly, flame-retardant, and explosion-proof, its maintenance-free nature reduces costs.
Small Size and Light Weight: Facilitates easy transportation and installation, optimizing space usage.
After-Sales Service:
Offering comprehensive pre-sales consultation and optimal program design services.
Enjoy free repair or replacement for product quality-related faults during the warranty period.
Avail lifelong technical support and after-sales service, ensuring complete peace of mind for customers.
Application Scenario:
Substation, Dockyard, City Life
Electric Power Plant Wind Power Railroads
Factory Scene:
Certificates:
FAQ:
1. Are you a trading company or manufacturer?
We are a professional factory boasting 10 years of expertise in high and low voltage switchgears, substations, transformers, and various electrical equipment, including vacuum circuit breakers and load break switches.
Our factory proudly serves as an outstanding supplier to the State Grid Corporation of China.
2. Do you accept customized services?
We proudly offer comprehensive OEM/ODM services, allowing your brand's logo to be elegantly imprinted on our product. Our highly skilled technical and quotation team is at your service, crafting a meticulously tailored project that aligns perfectly with your specific drawings and parameters.
3. What is your Minimum Order Quantity (MOQ)?
Our Minimum Order Quantity is conveniently set at just 1 piece.
4. What is your estimated delivery lead time?
The delivery lead time varies based on your product specifications and order quantity. Typically, we can fulfill orders within a swift 5 to 10 working days timeframe.
5. How do you address quality concerns?
Kindly provide detailed photographs of any quality issues encountered. Our dedicated technical and quality testing team will conduct a thorough analysis and offer a satisfactory resolution within a prompt 2-day period.
6. What are your payment terms?
We require a 30% T/T advance deposit, with the remaining 70% due before shipment. We also accept payments via West Union and L/C.