10kv/20kv/35kv 0.4 Oil-Immersed Three-Phase Transformer
Introducing the sophisticated 20kV oil-immersed transformer, a pinnacle of electrical engineering, utilizing superior insulating oil as its medium. It boasts an array of crucial components: a robust iron core, precision coil, versatile voltage regulating switch, and a resilient oil tank. This transformer excels in voltage modulation and alternating current energy transmission. Its compact design, affordable pricing, and exceptional weather resistance make it an indispensable asset across diverse sectors including power systems, industrial operations, mining enterprises, transportation networks, telecommunications, and cutting-edge research facilities.
nominal
capacity
|
high
voltage side
|
High voltage
tap range
|
low
voltage side
|
Connection
group labeling
|
No-
load loss
|
Load Loss |
No-load
current
|
Short Circuit
Impedance
|
30KVA |
11KV
10.5KV
10KV 6.3KV 6KV |
±5
±2×2.5%
|
0.4KV
0.69KV
|
Dyn11
Yyn0
|
100W | 630/600W | 2.3% | 4% |
50KVA | 130W | 910/870W | 2.0% | 4% | ||||
63KVA | 150W | 1090/1040W | 1.9% | 4% | ||||
80KVA | 180W | 1310/1250W | 1.9% | 4% | ||||
100KVA | 200W | 1580/1500W | 1.8% | 4% | ||||
125KVA | 240W | 1890/1800W | 1.7% | 4% | ||||
160KVA | 280W | 2310/2200W | 1.6% | 4% | ||||
200KVA | 340W | 2730/2600W | 1.5% | 4% | ||||
250KVA | 400W | 3200/3050W | 1.4% | 4% | ||||
315KVA | 480W | 3830/3650W | 1.4% | 4% | ||||
400KVA | 570W | 4520/4300W | 1.3% | 4% | ||||
500KVA | 680W | 5410/5150W | 1.2% | 4% | ||||
630KVA | 810W | 6200W | 1.1% | 4.5% | ||||
800KVA | 960W | 7500W | 1.0% | 4.5% | ||||
1000KVA | 1150W | 10300W | 1.0% | 4.5% | ||||
1250KVA | 1360W | 12000W | 0.9% | 4.5% | ||||
1600KVA | 1640W | 14500W | 0.8% | 4.5% | ||||
2000KVA | 1960W | 19800W | 0.8% | 5% | ||||
2500KVA | 2310W | 23000W | 0.7% | 5% |
Installation Instructions:
1. Installation form:
Our 20kV oil-immersed transformers offer versatile installation options, including pole-mounted setups, robust outdoor configurations, and seamless indoor installations, catering to a variety of environmental and infrastructural needs.
For outdoor installations, secure the transformer on a reinforced concrete foundation. Indoor installations require ensuring the transformer's frontal alignment with the cabinet, achieving a snug fit with the distribution panel, devoid of any gaps.
2. Installation steps:
During transformer placement, utilize specially designed force points to ensure stability and employ anti-slip measures for enhanced safety.
Maintain precise control over the transformer's body inclination during transit and installation: limit the long axis to within 15° and the short axis to within 10° to ensure optimal performance.
During the installation, it is crucial to ensure that the gaps between each component are neither too tight nor too loose, achieving an ideal fit for optimal functionality.
For terminal installations, carefully select suitable insulation disks that match the actual conditions and ensure accurate wiring.
3. Attachment installation:
When installing critical accessories like gas relays, pressure relief devices, moisture absorbers, and sleeves, adhere strictly to relevant standards and manufacturer guidelines to guarantee seamless integration and performance.
Certificates: