10kv/20kv/35kv 0.4 Oil-Immersed Three-Phase Transformer
Introducing our 20kV Oil Immersed Transformer, a state-of-the-art electrical apparatus that utilizes the exceptional insulating properties of oil as its core medium. This sophisticated system integrates an iron core, coil, voltage regulation switch, and robust oil tank. Designed to efficiently modulate voltage and transmit alternating current, our transformer stands out with its compact design, affordability, and unparalleled resilience against harsh weather conditions. It is the optimal choice for power systems, industrial and mining operations, transportation networks, postal and telecommunications services, and cutting-edge research institutions.
nominal
capacity
|
high
voltage side
|
High voltage
tap range
|
low
voltage side
|
Connection
group labeling
|
No-
load loss
|
Load Loss |
No-load
current
|
Short Circuit
Impedance
|
30KVA |
11KV
10.5KV
10KV 6.3KV 6KV |
±5
±2×2.5%
|
0.4KV
0.69KV
|
Dyn11
Yyn0
|
100W | 630/600W | 2.3% | 4% |
50KVA | 130W | 910/870W | 2.0% | 4% | ||||
63KVA | 150W | 1090/1040W | 1.9% | 4% | ||||
80KVA | 180W | 1310/1250W | 1.9% | 4% | ||||
100KVA | 200W | 1580/1500W | 1.8% | 4% | ||||
125KVA | 240W | 1890/1800W | 1.7% | 4% | ||||
160KVA | 280W | 2310/2200W | 1.6% | 4% | ||||
200KVA | 340W | 2730/2600W | 1.5% | 4% | ||||
250KVA | 400W | 3200/3050W | 1.4% | 4% | ||||
315KVA | 480W | 3830/3650W | 1.4% | 4% | ||||
400KVA | 570W | 4520/4300W | 1.3% | 4% | ||||
500KVA | 680W | 5410/5150W | 1.2% | 4% | ||||
630KVA | 810W | 6200W | 1.1% | 4.5% | ||||
800KVA | 960W | 7500W | 1.0% | 4.5% | ||||
1000KVA | 1150W | 10300W | 1.0% | 4.5% | ||||
1250KVA | 1360W | 12000W | 0.9% | 4.5% | ||||
1600KVA | 1640W | 14500W | 0.8% | 4.5% | ||||
2000KVA | 1960W | 19800W | 0.8% | 5% | ||||
2500KVA | 2310W | 23000W | 0.7% | 5% |
Installation Instructions:
1. Installation Form:
Choose from versatile installation options for our 20kV oil-immersed transformers, including pole-mounted, outdoor, and indoor installation methods to suit your specific needs.
For outdoor installation, ensure a stable setup on a reinforced concrete foundation. For indoor installations, align the transformer precisely so that it is flush with the cabinet front and securely attached to the distribution panel, leaving no gaps.
2. Installation Steps:
When positioning the transformer, employ designated force points tailored for this product, and ensure anti-slip measures are implemented for optimal safety.
Maintain meticulous control over the transformer's inclination during transport and installation, adhering to a maximum of 15° along the long axis and 10° along the short axis.
Pay close attention to the spacing between components during setup, ensuring neither excessive tightness nor looseness for optimal performance.
Select appropriate insulation disks for terminal installations based on real-world conditions, ensuring precise and effective wiring.
3. Attachment Installation:
Ensure the precise installation of accessories such as gas relays, pressure relief devices, moisture absorbers, and sleeves, in accordance with stringent standards and manufacturer guidelines.
Certificates: