Customization: | Available |
---|---|
Application: | Power, Instrument, Rectifier |
Phase: | Three |
Shipping Cost: | Contact the supplier about freight and estimated delivery time. |
---|
Payment Methods: |
![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() |
---|---|
Support payments in USD |
Secure payments: | Every payment you make on Made-in-China.com is protected by the platform. |
---|
Refund policy: | Claim a refund if your order doesn't ship, is missing, or arrives with product issues. |
---|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Experience the power of our versatile 10kv/20kv/35kv 0.4 Oil-Immersed Three-Phase Transformer, a marvel of engineering designed to meet all your electrical needs with precision and efficiency.
Discover the cutting-edge 20kV oil immersed transformer- a pinnacle of electrical innovation. This transformative device utilizes high-grade insulating oil, comprising an expertly crafted iron core, precision coils, efficient voltage-regulating switches, and a robust oil tank. Designed to seamlessly alter voltage and transmit alternating current energy, it boasts a compact size, cost-effectiveness, and remarkable weather resistance. This adaptable transformer is ideally suited for power systems, industrial operations, transportation, postal and telecommunications sectors, as well as scientific research institutions.
nominal
capacity
|
high
voltage side
|
High voltage
tap range
|
low
voltage side
|
Connection
group labeling
|
No-
load loss
|
Load Loss |
No-load
current
|
Short Circuit
Impedance
|
30KVA |
11KV
10.5KV
10KV 6.3KV 6KV |
±5
±2×2.5%
|
0.4KV
0.69KV
|
Dyn11
Yyn0
|
100W | 630/600W | 2.3% | 4% |
50KVA | 130W | 910/870W | 2.0% | 4% | ||||
63KVA | 150W | 1090/1040W | 1.9% | 4% | ||||
80KVA | 180W | 1310/1250W | 1.9% | 4% | ||||
100KVA | 200W | 1580/1500W | 1.8% | 4% | ||||
125KVA | 240W | 1890/1800W | 1.7% | 4% | ||||
160KVA | 280W | 2310/2200W | 1.6% | 4% | ||||
200KVA | 340W | 2730/2600W | 1.5% | 4% | ||||
250KVA | 400W | 3200/3050W | 1.4% | 4% | ||||
315KVA | 480W | 3830/3650W | 1.4% | 4% | ||||
400KVA | 570W | 4520/4300W | 1.3% | 4% | ||||
500KVA | 680W | 5410/5150W | 1.2% | 4% | ||||
630KVA | 810W | 6200W | 1.1% | 4.5% | ||||
800KVA | 960W | 7500W | 1.0% | 4.5% | ||||
1000KVA | 1150W | 10300W | 1.0% | 4.5% | ||||
1250KVA | 1360W | 12000W | 0.9% | 4.5% | ||||
1600KVA | 1640W | 14500W | 0.8% | 4.5% | ||||
2000KVA | 1960W | 19800W | 0.8% | 5% | ||||
2500KVA | 2310W | 23000W | 0.7% | 5% |
Installation Instructions:
1. Installation form:
Choose from several installation methods for the 20kV oil immersed transformers, including pole-mounted setups, robust outdoor installations, and seamless indoor configurations, each designed for specific situational needs.
For outdoor installations, secure the transformer on a reinforced concrete foundation. Indoors, ensure it aligns perfectly with the cabinet front, maintaining a seamless fit against the distribution panel.
2. Installation steps:
When positioning the transformer, employ specially designed force points, and implement strategic anti-slip measures to guarantee stability.
During transport and installation, carefully manage the transformer's inclination, keeping it within a specified range-no more than 15° along its length and 10° across its width-to ensure safety and performance.
Maintain optimal spacing between components during installation to prevent overly tight or loose fittings, ensuring efficient performance.
Select appropriate insulation disks for terminal installation based on practical requirements and ensure precise wiring for reliable operation.
3. Attachment installation:
When attaching components such as gas relays, pressure relief devices, moisture absorbers, and sleeves, adhere to stringent standards and manufacturer specifications for optimal functionality.
Certificates: