Customization: | Available |
---|---|
Application: | Power, Instrument, Rectifier |
Phase: | Three |
Shipping Cost: | Contact the supplier about freight and estimated delivery time. |
---|
Payment Methods: |
![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() |
---|---|
Support payments in USD |
Secure payments: | Every payment you make on Made-in-China.com is protected by the platform. |
---|
Refund policy: | Claim a refund if your order doesn't ship, is missing, or arrives with product issues. |
---|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
10kv/20kv/35kv 0.4 Oil-Immersed Three-Phase Transformer
Our 20kV oil-immersed transformer is an exceptional piece of electrical equipment, utilizing high-quality insulating oil as a medium to ensure optimal performance. With a meticulously engineered iron core, coil, voltage regulating switch, and oil tank, this transformer is designed to efficiently alter voltage and seamlessly transmit alternating current energy. Boasting compactness, affordability, and outstanding weather resistance, it stands as a testament to reliability and is extensively employed across power systems, industrial sectors, mining enterprises, transportation networks, postal and telecommunications departments, and scientific research institutions.
nominal
capacity
|
high
voltage side
|
High voltage
tap range
|
low
voltage side
|
Connection
group labeling
|
No-
load loss
|
Load Loss |
No-load
current
|
Short Circuit
Impedance
|
30KVA |
11KV
10.5KV
10KV 6.3KV 6KV |
±5
±2×2.5%
|
0.4KV
0.69KV
|
Dyn11
Yyn0
|
100W | 630/600W | 2.3% | 4% |
50KVA | 130W | 910/870W | 2.0% | 4% | ||||
63KVA | 150W | 1090/1040W | 1.9% | 4% | ||||
80KVA | 180W | 1310/1250W | 1.9% | 4% | ||||
100KVA | 200W | 1580/1500W | 1.8% | 4% | ||||
125KVA | 240W | 1890/1800W | 1.7% | 4% | ||||
160KVA | 280W | 2310/2200W | 1.6% | 4% | ||||
200KVA | 340W | 2730/2600W | 1.5% | 4% | ||||
250KVA | 400W | 3200/3050W | 1.4% | 4% | ||||
315KVA | 480W | 3830/3650W | 1.4% | 4% | ||||
400KVA | 570W | 4520/4300W | 1.3% | 4% | ||||
500KVA | 680W | 5410/5150W | 1.2% | 4% | ||||
630KVA | 810W | 6200W | 1.1% | 4.5% | ||||
800KVA | 960W | 7500W | 1.0% | 4.5% | ||||
1000KVA | 1150W | 10300W | 1.0% | 4.5% | ||||
1250KVA | 1360W | 12000W | 0.9% | 4.5% | ||||
1600KVA | 1640W | 14500W | 0.8% | 4.5% | ||||
2000KVA | 1960W | 19800W | 0.8% | 5% | ||||
2500KVA | 2310W | 23000W | 0.7% | 5% |
Installation Instructions:
1. Installation form:
Our versatile 20kV oil-immersed transformers can be installed using various methods, including pole-mounted installation, outdoor installation, or indoor transformer installation, ensuring flexibility to suit any environment.
For outdoor installations, secure the transformer on a reinforced concrete foundation. Indoors, ensure the transformer body aligns perfectly flush with the cabinet front and is snugly affixed to the distribution panel, leaving no room for gaps.
2. Installation steps:
Positioning the transformer requires utilizing specially designed force points, accompanied by necessary anti-slip measures to maintain stability and safety.
Maintain careful control over the transformer body's tilt during both transportation and installation, adhering to a maximum inclination of 15° along the long axis and 10° along the short axis.
During installation, ensure that all components are optimally spaced to avoid excessive tightness or looseness, which could impact performance.
Select the appropriate insulation disks for terminal installations based on actual conditions, ensuring precise and accurate wiring.
3. Attachment installation:
Fit accessories like gas relays, pressure relief devices, moisture absorbers, and sleeves in strict accordance with relevant standards and the manufacturer's requirements for optimal performance and safety.
Certificates: