10kV/20kV/35kV 0.4 Oil-Immersed Three-Phase Transformer
Introducing our 20kV Oil Immersed Transformer, an essential piece of electrical equipment designed to efficiently utilize insulating oil as its core medium. Comprising a robust iron core, intricately wound coil, adaptable voltage regulating switch, and a durable oil tank, this transformer excels in altering voltage levels and transmitting alternating current energy seamlessly. Its compact size, competitive pricing, and exceptional weather resistance make it an ideal choice across diverse sectors, including power systems, industrial and mining enterprises, transportation, postal and telecommunications departments, and research institutions.
nominal
capacity
|
high
voltage side
|
High voltage
tap range
|
low
voltage side
|
Connection
group labeling
|
No-
load loss
|
Load Loss |
No-load
current
|
Short Circuit
Impedance
|
30KVA |
11KV
10.5KV
10KV 6.3KV 6KV |
±5
±2×2.5%
|
0.4KV
0.69KV
|
Dyn11
Yyn0
|
100W | 630/600W | 2.3% | 4% |
50KVA | 130W | 910/870W | 2.0% | 4% | ||||
63KVA | 150W | 1090/1040W | 1.9% | 4% | ||||
80KVA | 180W | 1310/1250W | 1.9% | 4% | ||||
100KVA | 200W | 1580/1500W | 1.8% | 4% | ||||
125KVA | 240W | 1890/1800W | 1.7% | 4% | ||||
160KVA | 280W | 2310/2200W | 1.6% | 4% | ||||
200KVA | 340W | 2730/2600W | 1.5% | 4% | ||||
250KVA | 400W | 3200/3050W | 1.4% | 4% | ||||
315KVA | 480W | 3830/3650W | 1.4% | 4% | ||||
400KVA | 570W | 4520/4300W | 1.3% | 4% | ||||
500KVA | 680W | 5410/5150W | 1.2% | 4% | ||||
630KVA | 810W | 6200W | 1.1% | 4.5% | ||||
800KVA | 960W | 7500W | 1.0% | 4.5% | ||||
1000KVA | 1150W | 10300W | 1.0% | 4.5% | ||||
1250KVA | 1360W | 12000W | 0.9% | 4.5% | ||||
1600KVA | 1640W | 14500W | 0.8% | 4.5% | ||||
2000KVA | 1960W | 19800W | 0.8% | 5% | ||||
2500KVA | 2310W | 23000W | 0.7% | 5% |
Installation Instructions:
1. Installation form:
Our 20kV Oil Immersed Transformers are versatile in installation, offering options such as pole-mounted, outdoor, and indoor transformer installations to suit various environmental needs.
For outdoor installations, ensure the transformer is securely fastened on a reinforced concrete foundation. Indoor installations require the transformer body to be flush with the front of the cabinet, tightly aligned with the distribution panel to prevent any gaps.
2. Installation steps:
When positioning the transformer, utilize the specially designed force points and implement anti-slip measures to maintain stability.
Ensure the inclination of the transformer body remains within specified limits during transportation and installation (no more than 15° along the long axis and 10° on the short axis) to prevent operational issues.
During installation, meticulously adjust the gaps between components to prevent excessive tightness or looseness, ensuring optimal functionality.
Choose appropriate insulation disks based on actual conditions for terminal installations, ensuring correct wiring for safe operation.
3. Attachment installation:
When installing accessories like gas relays, pressure relief devices, moisture absorbers, and sleeves, adhere strictly to relevant standards and manufacturer guidelines to guarantee performance integrity.
Certificates: