10kv/20kv/35kv 0.4 Oil-Immersed Three-Phase Transformer
Introducing our 20kV Oil Immersed Transformer, a marvel of electrical engineering that employs insulating oil as its core medium. This powerhouse is comprised of an iron core, coil, voltage regulating switch, oil tank, and more, designed to efficiently transform voltage and facilitate the seamless transmission of alternating current energy. With its compact size, budget-friendly pricing, and robust weather resistance, this transformer is the top choice for power systems, industrial and mining sectors, transportation, postal and telecommunications, and esteemed scientific research institutions.
nominal
capacity
|
high
voltage side
|
High voltage
tap range
|
low
voltage side
|
Connection
group labeling
|
No-
load loss
|
Load Loss |
No-load
current
|
Short Circuit
Impedance
|
30KVA |
11KV
10.5KV
10KV 6.3KV 6KV |
±5
±2×2.5%
|
0.4KV
0.69KV
|
Dyn11
Yyn0
|
100W | 630/600W | 2.3% | 4% |
50KVA | 130W | 910/870W | 2.0% | 4% | ||||
63KVA | 150W | 1090/1040W | 1.9% | 4% | ||||
80KVA | 180W | 1310/1250W | 1.9% | 4% | ||||
100KVA | 200W | 1580/1500W | 1.8% | 4% | ||||
125KVA | 240W | 1890/1800W | 1.7% | 4% | ||||
160KVA | 280W | 2310/2200W | 1.6% | 4% | ||||
200KVA | 340W | 2730/2600W | 1.5% | 4% | ||||
250KVA | 400W | 3200/3050W | 1.4% | 4% | ||||
315KVA | 480W | 3830/3650W | 1.4% | 4% | ||||
400KVA | 570W | 4520/4300W | 1.3% | 4% | ||||
500KVA | 680W | 5410/5150W | 1.2% | 4% | ||||
630KVA | 810W | 6200W | 1.1% | 4.5% | ||||
800KVA | 960W | 7500W | 1.0% | 4.5% | ||||
1000KVA | 1150W | 10300W | 1.0% | 4.5% | ||||
1250KVA | 1360W | 12000W | 0.9% | 4.5% | ||||
1600KVA | 1640W | 14500W | 0.8% | 4.5% | ||||
2000KVA | 1960W | 19800W | 0.8% | 5% | ||||
2500KVA | 2310W | 23000W | 0.7% | 5% |
Installation Instructions:
1. Installation form:
Our 20kV oil-immersed transformers offer versatile installation options, accommodating pole-mounted setups, outdoor installations, or indoor placements, each tailored to fit your specific needs.
For outdoor installations, anchoring on a robust reinforced concrete foundation is crucial; indoors, ensure the transformer is aligned and seamlessly integrated with the distribution panel, eliminating any gaps for optimal performance.
2. Installation steps:
During installation, utilize designated force points engineered for stability, and incorporate anti-slip measures to guarantee secure placement.
Maintain a precise control over the inclination of the transformer during transport and installation, ensuring angles do not exceed 15° along the long axis and 10° along the short axis.
Pay meticulous attention to the spacing between components during assembly to prevent any excessive tightness or looseness, ensuring smooth operation.
When connecting terminals, select appropriate insulation disks based on the current setup, and execute wiring with precision for flawless connectivity.
3. Attachment installation:
Adhere to all relevant standards and manufacturer requirements when installing accessories like gas relays, pressure relief devices, moisture absorbers, and sleeves, ensuring optimal performance and compliance.
Certificates: