Presenting the robust and efficient 10kv/20kv/35kv 0.4 Oil-Immersed Three-Phase Transformer, designed for optimal performance and reliability in diverse electrical applications.
Introducing our advanced 20kV oil immersed transformer, a cutting-edge electrical solution leveraging insulating oil as a medium to efficiently manage voltage changes and transmit alternating current. Comprising a sophisticated assembly of iron core, coil, voltage regulating switch, and durable oil tank, this transformer stands out for its compact design, affordability, and exceptional durability against harsh weather conditions. Its versatility makes it an ideal choice for power systems, industrial enterprises, transportation sectors, telecommunications, and research institutions alike.
nominal
capacity
|
high
voltage side
|
High voltage
tap range
|
low
voltage side
|
Connection
group labeling
|
No-
load loss
|
Load Loss |
No-load
current
|
Short Circuit
Impedance
|
30KVA |
11KV
10.5KV
10KV 6.3KV 6KV |
±5
±2×2.5%
|
0.4KV
0.69KV
|
Dyn11
Yyn0
|
100W | 630/600W | 2.3% | 4% |
50KVA | 130W | 910/870W | 2.0% | 4% | ||||
63KVA | 150W | 1090/1040W | 1.9% | 4% | ||||
80KVA | 180W | 1310/1250W | 1.9% | 4% | ||||
100KVA | 200W | 1580/1500W | 1.8% | 4% | ||||
125KVA | 240W | 1890/1800W | 1.7% | 4% | ||||
160KVA | 280W | 2310/2200W | 1.6% | 4% | ||||
200KVA | 340W | 2730/2600W | 1.5% | 4% | ||||
250KVA | 400W | 3200/3050W | 1.4% | 4% | ||||
315KVA | 480W | 3830/3650W | 1.4% | 4% | ||||
400KVA | 570W | 4520/4300W | 1.3% | 4% | ||||
500KVA | 680W | 5410/5150W | 1.2% | 4% | ||||
630KVA | 810W | 6200W | 1.1% | 4.5% | ||||
800KVA | 960W | 7500W | 1.0% | 4.5% | ||||
1000KVA | 1150W | 10300W | 1.0% | 4.5% | ||||
1250KVA | 1360W | 12000W | 0.9% | 4.5% | ||||
1600KVA | 1640W | 14500W | 0.8% | 4.5% | ||||
2000KVA | 1960W | 19800W | 0.8% | 5% | ||||
2500KVA | 2310W | 23000W | 0.7% | 5% |
Installation Instructions:
1. Installation form:
Our 20kV oil immersed transformers offer flexibility in installation, accommodating pole mounted, outdoor, and indoor configurations to suit your spatial and operational needs.
Outdoor installations require a secure foundation, ideally of reinforced concrete, while indoor installations should ensure the transformer aligns precisely with the cabinetry, seamlessly integrating with the distribution panel.
2. Installation steps:
Ensure the transformer is positioned using designated force points, employing anti-slip measures to maintain stability and security.
During transit and setup, manage the transformer's inclination within specified limits: a max of 15° in the long axis and 10° in the short axis, to safeguard against operational disruptions.
It is crucial to meticulously manage the spacing between components to ensure neither excessive tightness nor undesired looseness, thereby optimizing functionality.
Carefully select suitable insulation disks to match the specific requirements during terminal installation, ensuring precise wiring for optimal performance.
3. Attachment installation:
Install critical components like gas relays, pressure relief devices, and moisture absorbers in strict accordance with both relevant standards and the manufacturer's detailed specifications, securing peak performance.
Certificates: