10kv/20kv/35kv 0.4 Oil-Immersed Three-Phase Transformer
A 20kV oil-immersed transformer is a meticulously engineered piece of electrical equipment that employs insulating oil as its insulating medium, and it comprises an iron core, coil, voltage regulating switch, oil tank, among other essential components. This robust product is designed to efficiently convert voltages and transmit alternating current energy. Known for its compact design, budget-friendly pricing, and exceptional resistance to various weather conditions, this transformer is ideal for a wide range of applications. It is extensively utilized across power systems, industrial and mining enterprises, transportation, postal and telecommunications sectors, as well as in esteemed scientific research institutions.
nominal
capacity
|
high
voltage side
|
High voltage
tap range
|
low
voltage side
|
Connection
group labeling
|
No-
load loss
|
Load Loss |
No-load
current
|
Short Circuit
Impedance
|
30KVA |
11KV
10.5KV
10KV 6.3KV 6KV |
±5
±2×2.5%
|
0.4KV
0.69KV
|
Dyn11
Yyn0
|
100W | 630/600W | 2.3% | 4% |
50KVA | 130W | 910/870W | 2.0% | 4% | ||||
63KVA | 150W | 1090/1040W | 1.9% | 4% | ||||
80KVA | 180W | 1310/1250W | 1.9% | 4% | ||||
100KVA | 200W | 1580/1500W | 1.8% | 4% | ||||
125KVA | 240W | 1890/1800W | 1.7% | 4% | ||||
160KVA | 280W | 2310/2200W | 1.6% | 4% | ||||
200KVA | 340W | 2730/2600W | 1.5% | 4% | ||||
250KVA | 400W | 3200/3050W | 1.4% | 4% | ||||
315KVA | 480W | 3830/3650W | 1.4% | 4% | ||||
400KVA | 570W | 4520/4300W | 1.3% | 4% | ||||
500KVA | 680W | 5410/5150W | 1.2% | 4% | ||||
630KVA | 810W | 6200W | 1.1% | 4.5% | ||||
800KVA | 960W | 7500W | 1.0% | 4.5% | ||||
1000KVA | 1150W | 10300W | 1.0% | 4.5% | ||||
1250KVA | 1360W | 12000W | 0.9% | 4.5% | ||||
1600KVA | 1640W | 14500W | 0.8% | 4.5% | ||||
2000KVA | 1960W | 19800W | 0.8% | 5% | ||||
2500KVA | 2310W | 23000W | 0.7% | 5% |
Installation Instructions:
1. Installation form:
The installation forms for 20kV oil-immersed transformers are versatile and include pole-mounted installation, outdoor installation, and indoor transformer installation, among others.
When installed outdoors, ensure it is securely mounted on a reinforced concrete foundation. For indoor installations, ensure the transformer is seamlessly aligned with the front of the cabinet, closely adhering to the distribution panel without any visible gaps.
2. Installation steps:
During the placement of the transformer, utilize specially designed force points crafted for this product to ensure stability, incorporating anti-slip measures for optimal safety.
During transportation and installation, control the transformer's body inclination within specified limits (not exceeding 15° along the long axis and 10° along the short axis) for safe handling.
During installation, carefully monitor the spacing between each component to prevent over-tightening or excessive looseness, ensuring a flawless fit.
When setting up terminals, select appropriate insulation disks based on the actual conditions and ensure correct wiring to maintain functionality and safety.
3. Attachment installation:
When installing essential accessories such as gas relays, pressure relief devices, moisture absorbers, and sleeves, adhere strictly to relevant standards and manufacturer requirements to guarantee optimal performance.
Certificates: