Customization: | Available |
---|---|
Application: | Power, Instrument, Rectifier |
Phase: | Three |
Shipping Cost: | Contact the supplier about freight and estimated delivery time. |
---|
Payment Methods: |
![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() |
---|---|
Support payments in USD |
Secure payments: | Every payment you make on Made-in-China.com is protected by the platform. |
---|
Refund policy: | Claim a refund if your order doesn't ship, is missing, or arrives with product issues. |
---|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Experience the robust performance of our 10kv/20kv/35kv 0.4 Oil-Immersed Three-Phase Transformer, a pinnacle in energy conversion technology.
Our state-of-the-art 20kV oil-immersed transformer is a marvel of electrical engineering, utilizing premium insulating oil as its medium. Comprising an expertly crafted iron core, precise coil, reliable voltage regulating switch, and sturdy oil tank, this transformer excels at voltage alteration and seamless AC energy transmission. Boasting a compact form factor, competitive pricing, and exceptional durability against harsh weather, it finds versatile applications across power systems, industrial and mining sectors, transportation networks, postal and telecommunications, and esteemed research institutions.
nominal
capacity
|
high
voltage side
|
High voltage
tap range
|
low
voltage side
|
Connection
group labeling
|
No-
load loss
|
Load Loss |
No-load
current
|
Short Circuit
Impedance
|
30KVA |
11KV
10.5KV
10KV 6.3KV 6KV |
±5
±2×2.5%
|
0.4KV
0.69KV
|
Dyn11
Yyn0
|
100W | 630/600W | 2.3% | 4% |
50KVA | 130W | 910/870W | 2.0% | 4% | ||||
63KVA | 150W | 1090/1040W | 1.9% | 4% | ||||
80KVA | 180W | 1310/1250W | 1.9% | 4% | ||||
100KVA | 200W | 1580/1500W | 1.8% | 4% | ||||
125KVA | 240W | 1890/1800W | 1.7% | 4% | ||||
160KVA | 280W | 2310/2200W | 1.6% | 4% | ||||
200KVA | 340W | 2730/2600W | 1.5% | 4% | ||||
250KVA | 400W | 3200/3050W | 1.4% | 4% | ||||
315KVA | 480W | 3830/3650W | 1.4% | 4% | ||||
400KVA | 570W | 4520/4300W | 1.3% | 4% | ||||
500KVA | 680W | 5410/5150W | 1.2% | 4% | ||||
630KVA | 810W | 6200W | 1.1% | 4.5% | ||||
800KVA | 960W | 7500W | 1.0% | 4.5% | ||||
1000KVA | 1150W | 10300W | 1.0% | 4.5% | ||||
1250KVA | 1360W | 12000W | 0.9% | 4.5% | ||||
1600KVA | 1640W | 14500W | 0.8% | 4.5% | ||||
2000KVA | 1960W | 19800W | 0.8% | 5% | ||||
2500KVA | 2310W | 23000W | 0.7% | 5% |
Installation Instructions:
1. Installation form:
Our versatile 20kV oil-immersed transformers can be installed in various configurations, including pole-mounted setups, resilient outdoor installations, and secure indoor transformer placements.
For outdoor installations, ensure the transformer is anchored on a reinforced concrete foundation. Indoor setups must align the transformer body flush with the cabinet front, maintaining a seamless fit with the distribution panel.
2. Installation steps:
When positioning the transformer, employ the designated force points for optimal placement and implement anti-slip precautions to secure its stability.
During transportation and installation, carefully monitor the transformer body's inclination, keeping it within a controlled range of no more than 15° on the long axis and 10° on the short axis.
Ensure adequate spacing between components during installation to prevent overly tight or excessively loose connections.
Appropriately select insulation disks based on the prevailing conditions while wiring terminals, ensuring accuracy and safety.
3. Attachment installation:
Incorporate accessories such as gas relays, pressure relief devices, moisture absorbers, and sleeves with adherence to stringent standards and manufacturer guidelines for flawless operation.
Certificates: