Customization: | Available |
---|---|
Application: | Power, Instrument, Rectifier |
Phase: | Three |
Shipping Cost: | Contact the supplier about freight and estimated delivery time. |
---|
Payment Methods: |
![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() |
---|---|
Support payments in USD |
Secure payments: | Every payment you make on Made-in-China.com is protected by the platform. |
---|
Refund policy: | Claim a refund if your order doesn't ship, is missing, or arrives with product issues. |
---|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
10kv/20kv/35kv 0.4 Oil-Immersed Three-Phase Transformer
A state-of-the-art 20kV oil-immersed transformer is an essential piece of electrical equipment that utilizes insulating oil as its insulating medium. This comprehensive unit comprises an iron core, coil, voltage regulating switch, and oil tank, designed to adeptly modify voltage and transmit alternating current energy. Its compact size, affordability, and robust weather resistance make it an indispensable component across various sectors, including power systems, industrial and mining enterprises, transportation, postal and telecommunications, and scientific research institutions.
nominal
capacity
|
high
voltage side
|
High voltage
tap range
|
low
voltage side
|
Connection
group labeling
|
No-
load loss
|
Load Loss |
No-load
current
|
Short Circuit
Impedance
|
30KVA |
11KV
10.5KV
10KV 6.3KV 6KV |
±5
±2×2.5%
|
0.4KV
0.69KV
|
Dyn11
Yyn0
|
100W | 630/600W | 2.3% | 4% |
50KVA | 130W | 910/870W | 2.0% | 4% | ||||
63KVA | 150W | 1090/1040W | 1.9% | 4% | ||||
80KVA | 180W | 1310/1250W | 1.9% | 4% | ||||
100KVA | 200W | 1580/1500W | 1.8% | 4% | ||||
125KVA | 240W | 1890/1800W | 1.7% | 4% | ||||
160KVA | 280W | 2310/2200W | 1.6% | 4% | ||||
200KVA | 340W | 2730/2600W | 1.5% | 4% | ||||
250KVA | 400W | 3200/3050W | 1.4% | 4% | ||||
315KVA | 480W | 3830/3650W | 1.4% | 4% | ||||
400KVA | 570W | 4520/4300W | 1.3% | 4% | ||||
500KVA | 680W | 5410/5150W | 1.2% | 4% | ||||
630KVA | 810W | 6200W | 1.1% | 4.5% | ||||
800KVA | 960W | 7500W | 1.0% | 4.5% | ||||
1000KVA | 1150W | 10300W | 1.0% | 4.5% | ||||
1250KVA | 1360W | 12000W | 0.9% | 4.5% | ||||
1600KVA | 1640W | 14500W | 0.8% | 4.5% | ||||
2000KVA | 1960W | 19800W | 0.8% | 5% | ||||
2500KVA | 2310W | 23000W | 0.7% | 5% |
Installation Instructions:
1. Installation form:
The installation options for 20kV oil-immersed transformers are versatile, including pole-mounted installation, outdoor installation, and indoor transformer setup.
For outdoor installations, secure the unit on a reinforced concrete foundation; for indoor setups, ensure the transformer aligns perfectly with the cabinet front and adheres snugly to the distribution panel, leaving no gaps.
2. Installation steps:
Use specified force points for positioning the transformer, while implementing necessary anti-slip measures to ensure stability and safety.
Maintain the transformer's body inclination within specific limits during transit and installation (no more than 15° along the long axis and no more than 10° along the short axis).
When installing, pay close attention to the spacing between parts to avoid excessive tightness or looseness, ensuring optimal performance.
Select appropriate insulation disks based on the actual situation for terminal installation and ensure correct wiring.
3. Attachment installation:
Ensure that the installation of accessories, such as gas relays, pressure relief devices, moisture absorbers, and sleeves, adheres strictly to relevant standards and manufacturer guidelines.
Certificates: