10kv/20kv/35kv 0.4 Oil-Immersed Three-Phase Transformer
The 20kV oil-immersed transformer is a marvel of electrical engineering that harnesses the power of insulating oil to elevate and transmit alternating current energy. With an intricate blend of iron cores, coils, voltage regulating switches, and robust oil tanks, this transformer is a quintessential component for voltage transformation. Its compact design, affordability, and exceptional weather resilience make it an indispensable asset across diverse domains such as power systems, industrial and mining sectors, transportation, postal and telecommunication departments, as well as esteemed research institutions.
nominal
capacity
|
high
voltage side
|
High voltage
tap range
|
low
voltage side
|
Connection
group labeling
|
No-
load loss
|
Load Loss |
No-load
current
|
Short Circuit
Impedance
|
30KVA |
11KV
10.5KV
10KV 6.3KV 6KV |
±5
±2×2.5%
|
0.4KV
0.69KV
|
Dyn11
Yyn0
|
100W | 630/600W | 2.3% | 4% |
50KVA | 130W | 910/870W | 2.0% | 4% | ||||
63KVA | 150W | 1090/1040W | 1.9% | 4% | ||||
80KVA | 180W | 1310/1250W | 1.9% | 4% | ||||
100KVA | 200W | 1580/1500W | 1.8% | 4% | ||||
125KVA | 240W | 1890/1800W | 1.7% | 4% | ||||
160KVA | 280W | 2310/2200W | 1.6% | 4% | ||||
200KVA | 340W | 2730/2600W | 1.5% | 4% | ||||
250KVA | 400W | 3200/3050W | 1.4% | 4% | ||||
315KVA | 480W | 3830/3650W | 1.4% | 4% | ||||
400KVA | 570W | 4520/4300W | 1.3% | 4% | ||||
500KVA | 680W | 5410/5150W | 1.2% | 4% | ||||
630KVA | 810W | 6200W | 1.1% | 4.5% | ||||
800KVA | 960W | 7500W | 1.0% | 4.5% | ||||
1000KVA | 1150W | 10300W | 1.0% | 4.5% | ||||
1250KVA | 1360W | 12000W | 0.9% | 4.5% | ||||
1600KVA | 1640W | 14500W | 0.8% | 4.5% | ||||
2000KVA | 1960W | 19800W | 0.8% | 5% | ||||
2500KVA | 2310W | 23000W | 0.7% | 5% |
Installation Instructions:
1. Installation form:
Our 20kV oil-immersed transformers offer versatile installation options, including pole-mounted setups, outdoor installations, and indoor placements, providing flexibility to suit various environments.
For outdoor installations, secure the transformer on a reinforced concrete foundation; indoors, align the transformer body seamlessly with the cabinet front, ensuring a snug fit against the distribution panel.
2. Installation steps:
When positioning the transformer, utilize specially designed force points and implement anti-slip measures to ensure stability and safety.
Maintain the transformer's body inclination within specified limits during transport and installation, with a maximum of 15° in the long axis and 10° in the short axis, to ensure optimal performance.
Pay careful attention to the gaps between parts during installation to prevent excessive tightness or looseness, ensuring seamless operation.
Select appropriate insulation disks for terminal installation based on the actual conditions, ensuring correct and secure wiring.
3. Attachment installation:
Installation of accessories such as gas relays, pressure relief devices, moisture absorbers, and sleeves should adhere strictly to relevant standards and manufacturer specifications for optimal performance.
Certificates: