Customization: | Available |
---|---|
Application: | Power, Instrument, Rectifier |
Phase: | Three |
Shipping Cost: | Contact the supplier about freight and estimated delivery time. |
---|
Payment Methods: |
![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() |
---|---|
Support payments in USD |
Secure payments: | Every payment you make on Made-in-China.com is protected by the platform. |
---|
Refund policy: | Claim a refund if your order doesn't ship, is missing, or arrives with product issues. |
---|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
10kv/20kv/35kv 0.4 Oil-Immersed Three-Phase Transformer
The 20kV oil immersed transformer represents a pinnacle of electrical engineering, utilizing premium insulating oil as its medium. Comprising an iron core, coil, voltage regulating switch, and robust oil tank, it adeptly transforms voltage levels while efficiently transmitting alternating current energy. With its compact design, competitive pricing, and impressive weather resilience, this transformer is indispensable across power systems, industrial sectors, mining enterprises, transport networks, postal and telecom sectors, and scientific research facilities.
nominal
capacity
|
high
voltage side
|
High voltage
tap range
|
low
voltage side
|
Connection
group labeling
|
No-
load loss
|
Load Loss |
No-load
current
|
Short Circuit
Impedance
|
30KVA |
11KV
10.5KV
10KV 6.3KV 6KV |
±5
±2×2.5%
|
0.4KV
0.69KV
|
Dyn11
Yyn0
|
100W | 630/600W | 2.3% | 4% |
50KVA | 130W | 910/870W | 2.0% | 4% | ||||
63KVA | 150W | 1090/1040W | 1.9% | 4% | ||||
80KVA | 180W | 1310/1250W | 1.9% | 4% | ||||
100KVA | 200W | 1580/1500W | 1.8% | 4% | ||||
125KVA | 240W | 1890/1800W | 1.7% | 4% | ||||
160KVA | 280W | 2310/2200W | 1.6% | 4% | ||||
200KVA | 340W | 2730/2600W | 1.5% | 4% | ||||
250KVA | 400W | 3200/3050W | 1.4% | 4% | ||||
315KVA | 480W | 3830/3650W | 1.4% | 4% | ||||
400KVA | 570W | 4520/4300W | 1.3% | 4% | ||||
500KVA | 680W | 5410/5150W | 1.2% | 4% | ||||
630KVA | 810W | 6200W | 1.1% | 4.5% | ||||
800KVA | 960W | 7500W | 1.0% | 4.5% | ||||
1000KVA | 1150W | 10300W | 1.0% | 4.5% | ||||
1250KVA | 1360W | 12000W | 0.9% | 4.5% | ||||
1600KVA | 1640W | 14500W | 0.8% | 4.5% | ||||
2000KVA | 1960W | 19800W | 0.8% | 5% | ||||
2500KVA | 2310W | 23000W | 0.7% | 5% |
Installation Instructions:
1. Installation form:
Our 20kV oil immersed transformers offer versatile installation options including pole-mounted setups, exterior outdoor installations, and indoor configurations, catering to diverse environmental needs.
For outdoor installations, secure the transformer on a reinforced concrete foundation. Indoor installations require precise alignment, ensuring the body is flush with the cabinet front, seamlessly integrated without gaps.
2. Installation steps:
Once the transformer is positioned, utilize specially designed force points, implementing effective anti-slip measures to guarantee stability.
During both transportation and installation, maintain the transformer's inclination within safe limits (no more than 15° longitudinally and 10° laterally) to ensure integrity.
Ensure appropriate spacing between components during installation to prevent excessive tightness or looseness, maintaining operational efficiency.
Select the appropriate insulation disks for terminal installations, ensuring correct wiring according to situational demands.
3. Attachment installation:
For accessories like gas relays, pressure relief devices, and moisture absorbers, adherence to relevant standards and manufacturer guidelines is imperative for optimal functionality.
Certificates: