Customization: | Available |
---|---|
Application: | Power, Instrument, Rectifier |
Phase: | Three |
Shipping Cost: | Contact the supplier about freight and estimated delivery time. |
---|
Payment Methods: |
|
---|---|
Support payments in USD |
Secure payments: | Every payment you make on Made-in-China.com is protected by the platform. |
---|
Refund policy: | Claim a refund if your order doesn't ship, is missing, or arrives with product issues. |
---|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Introducing our robust and reliable 10kv/20kv/35kv 0.4 Oil-Immersed Three-Phase Transformer, designed to deliver optimal performance under the most demanding conditions.
Our exceptional 20kV oil-immersed transformer is an ingenious piece of electrical equipment, utilizing insulating oil as a medium to provide a fortified barrier. Comprising of an iron core, coil, voltage regulating switch, and oil tank, it is masterfully engineered to alter voltage and efficiently transmit alternating current energy. It boasts a compact design, competitive pricing, and unparalleled weather resistance, making it a preferred choice across power systems, industrial and mining enterprises, transportation sectors, postal and telecommunications departments, as well as in cutting-edge scientific research institutions.
nominal
capacity
|
high
voltage side
|
High voltage
tap range
|
low
voltage side
|
Connection
group labeling
|
No-
load loss
|
Load Loss |
No-load
current
|
Short Circuit
Impedance
|
30KVA |
11KV
10.5KV
10KV 6.3KV 6KV |
±5
±2×2.5%
|
0.4KV
0.69KV
|
Dyn11
Yyn0
|
100W | 630/600W | 2.3% | 4% |
50KVA | 130W | 910/870W | 2.0% | 4% | ||||
63KVA | 150W | 1090/1040W | 1.9% | 4% | ||||
80KVA | 180W | 1310/1250W | 1.9% | 4% | ||||
100KVA | 200W | 1580/1500W | 1.8% | 4% | ||||
125KVA | 240W | 1890/1800W | 1.7% | 4% | ||||
160KVA | 280W | 2310/2200W | 1.6% | 4% | ||||
200KVA | 340W | 2730/2600W | 1.5% | 4% | ||||
250KVA | 400W | 3200/3050W | 1.4% | 4% | ||||
315KVA | 480W | 3830/3650W | 1.4% | 4% | ||||
400KVA | 570W | 4520/4300W | 1.3% | 4% | ||||
500KVA | 680W | 5410/5150W | 1.2% | 4% | ||||
630KVA | 810W | 6200W | 1.1% | 4.5% | ||||
800KVA | 960W | 7500W | 1.0% | 4.5% | ||||
1000KVA | 1150W | 10300W | 1.0% | 4.5% | ||||
1250KVA | 1360W | 12000W | 0.9% | 4.5% | ||||
1600KVA | 1640W | 14500W | 0.8% | 4.5% | ||||
2000KVA | 1960W | 19800W | 0.8% | 5% | ||||
2500KVA | 2310W | 23000W | 0.7% | 5% |
Installation Instructions:
1. Installation form:
Our versatile 20kV oil-immersed transformers can be installed using various methods such as pole-mounted, outdoor, or indoor installations, catering to your diverse operational needs.
For outdoor setups, ensure a sturdy installation on a reinforced concrete foundation; indoors, align the transformer precisely with the cabinet front, securing it to the distribution panel with no visible gaps.
2. Installation steps:
During setup, employ specific force points designed for the transformer and implement anti-slip measures to ensure stability.
Maintain a controlled inclination of the transformer body within specified ranges during transport and installation, not exceeding 15° in the long axis and 10° in the short axis.
Pay careful attention to spacing during installation, ensuring components fit neither too tightly nor too loosely.
For terminal installation, select appropriate insulation disks based on actual conditions and ensure correct wiring configurations.
3. Attachment installation:
When affixing accessories like gas relays, pressure relief devices, moisture absorbers, and sleeves, adhere strictly to relevant standards and manufacturer guidelines to ensure optimal performance.
Certificates: