Epoxy resin dry-type transformer
Delivering power solutions that are not only safe and efficient but also eco-friendly and energy-saving.
parameter term |
parameter values |
rated voltage |
Various specifications available, such as 20KV, 10KV, 6KV, etc. |
Capacity range |
Various specifications are available, such as 500KVA, 630KVA, 800KVA, 1250KVA, etc. |
Cooling Method |
Natural air-cooled/forced air-cooled (according to specific models) |
Insulation material |
Epoxy resin or other high-performance insulating materials |
Protection class |
IPXX (according to the specific model, need to mark the specific level) |
Winding type |
Foil winding structure (low voltage) / "trapezoidal" segmented layer structure (high voltage) |
Core material |
High quality cold rolled grain oriented silicon steel sheet |
Technical Data Sheet for 6KV, 10KV Class 10 Dry Type Non-Excited Regulated Distribution Transformer |
nominal capacity |
Connection
group labeling
|
Voltage combination |
No-load
current
|
No-
load loss
|
Load Losses at Different Insulation Thermal Ratings |
Short Circuit
Impedance
|
B(100ºC) |
F(120ºC) |
H(145ºC) |
30KVA |
Yyn0
Dyn11 |
6-11±2×2.5%/0.4 |
2.1 |
190 |
670 |
710 |
760 |
4.0 |
50KVA |
2.1 |
270 |
940 |
1000 |
1070 |
4.0 |
80KVA |
1.6 |
370 |
1290 |
1380 |
1480 |
4.0 |
100KVA |
1.6 |
400 |
1480 |
1570 |
1690 |
4.0 |
125KVA |
1.5 |
470 |
1740 |
1850 |
1980 |
4.0 |
160KVA |
1.5 |
540 |
2000 |
2130 |
2280 |
4.0 |
200KVA |
1.3 |
620 |
2370 |
2530 |
2710 |
4.0 |
250KVA |
1.3 |
720 |
2590 |
2760 |
2960 |
4.0 |
315KVA |
1.1 |
880 |
3270 |
3470 |
3730 |
4.0 |
400KVA |
1.1 |
980 |
3750 |
3990 |
4280 |
4.0 |
500KVA |
1.1 |
1160 |
4590 |
4880 |
5230 |
4.0 |
630KVA |
0.9 |
1340 |
5530 |
5880 |
6290 |
4.0 |
630KVA |
0.9 |
1300 |
5610 |
5960 |
6400 |
6.0 |
800KVA |
0.9 |
1520 |
6550 |
6960 |
7460 |
6.0 |
1000KVA |
0.9 |
1770 |
7650 |
8130 |
8760 |
6.0 |
1250KVA |
0.9 |
2090 |
9100 |
9690 |
10370 |
6.0 |
1600KVA |
0.9 |
2450 |
11050 |
11730 |
12580 |
6.0 |
2000KVA |
0.9 |
3050 |
13600 |
14450 |
15560 |
6.0 |
2500KVA |
0.7 |
3600 |
16150 |
17170 |
18450 |
6.0 |
Basic Anatomy of the Dry-Type Transformer
1. Iron Core: Crafted from silicon steel sheets, the iron core forms the magnetic circuit of the transformer, expertly channeling magnetic flux.
2. Winding: Comprising high-voltage and low-voltage windings, these are intricately wound around the iron core, facilitating seamless energy conversion and transmission.
3. Insulating Cylinder: Positioned between the high and low voltage coils, this component enhances electrical insulation, ensuring the transformer's safe and reliable operation.
4. Pads: These provide essential support and stabilization to the coils, maintaining their structural integrity and shape.
5. Fasteners: These are crucial for connecting and securing each part of the transformer, designed with anti-loosening features for enhanced reliability.
Product Description:
Overview:
The 10kV dry-type transformer is distinguished by its core and windings being uninfluenced by insulating liquid. This design ensures unparalleled safety, fire prevention, and pollution-free operation, making it an indispensable asset across industrial, commercial, and civil power systems.
Main Features:
Unmatched Safety Performance: Fireproof and pollution-free, this transformer operates safely in load centers, significantly enhancing system security.
Exceptional Mechanical Strength: Boasting strong short-circuit resilience, minimal partial discharge, robust thermal stability, and an extended service life.
Noteworthy Energy-Saving Benefits: Designed for low loss, low noise, and high efficiency, it fully complies with contemporary energy-saving and environmental standards.
Outstanding Heat Dissipation: With superior heat dissipation and operating capacity, forced air-cooling enhances operation capabilities.
Robust Environmental Adaptability: Featuring excellent moisture-proof properties, it adapts seamlessly to high humidity and harsh conditions.
Minimal Maintenance Costs: Environmentally friendly, flame retardant, and explosion-proof attributes ensure reduced operation and maintenance expenditures, being maintenance-free.
Compact and Lightweight: Facilitates easy transport and installation while optimizing space utilization.
After-sales Service:
Offering extensive pre-sales consulting and bespoke program design services.
Warranty period includes complimentary repair or replacement services for quality-related faults.
Lifetime technical support and after-sales assistance provided to ensure customer satisfaction without concerns.
Factory Environment:
Certificates:
FAQ:
1. Are you a trading company or manufacturer?
We are a leading factory with a decade of expertise in High and Low voltage switchgears, substations, transformers, cable distribution boxes, and diverse electrical equipment such as vacuum circuit breakers and load break switches.
Our factory is a distinguished supplier to the State Grid Corporation of China.
2. Do you accept customized service?
Yes, we provide OEM/ODM services, including logo printing on products. Our skilled technical and quotation teams deliver tailored projects based on your specifications.
3. What is your MOQ?
We are pleased to offer a minimum order quantity (MOQ) of just one piece!
4. What is the estimated delivery lead time for your orders?
The delivery timeframe is largely determined by your specific product requirements and order volume. In most cases, you can expect a swift turnaround of 5 to 10 working days.
5. What measures do you take to address and resolve any quality issues?
To effectively address quality concerns, kindly provide us with comprehensive photographs highlighting the issues. Our expert technical and quality assurance team will conduct a thorough analysis and offer you a satisfactory solution within just two days.
6. Could you please elaborate on your terms of payment?
Our payment terms include a 30% T/T deposit in advance, with the remaining 70% due before shipment. We also accommodate payments via Western Union and L/C.