Customization: | Available |
---|---|
Application: | Power, Instrument, Rectifier |
Phase: | Three |
Shipping Cost: | Contact the supplier about freight and estimated delivery time. |
---|
Payment Methods: |
![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() |
---|---|
Support payments in USD |
Secure payments: | Every payment you make on Made-in-China.com is protected by the platform. |
---|
Refund policy: | Claim a refund if your order doesn't ship, is missing, or arrives with product issues. |
---|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Introducing the 10kv/20kv/35kv 0.4 Oil-Immersed Three-Phase Transformer: a robust and efficient solution designed to meet the demands of modern power systems.
The 20kV Oil-Immersed Transformer stands as a pinnacle of electrical engineering, utilizing high-quality insulating oil as its medium and featuring components such as an iron core, coil, voltage regulating switch, and oil tank. This transformer is engineered for voltage transformation and the efficient transmission of alternating current energy. Its compact design, affordability, and remarkable weather resistance make it an ideal choice for power systems, industrial and mining enterprises, transportation, telecommunications, and scientific research institutions.
nominal
capacity
|
high
voltage side
|
High voltage
tap range
|
low
voltage side
|
Connection
group labeling
|
No-
load loss
|
Load Loss |
No-load
current
|
Short Circuit
Impedance
|
30KVA |
11KV
10.5KV
10KV 6.3KV 6KV |
±5
±2×2.5%
|
0.4KV
0.69KV
|
Dyn11
Yyn0
|
100W | 630/600W | 2.3% | 4% |
50KVA | 130W | 910/870W | 2.0% | 4% | ||||
63KVA | 150W | 1090/1040W | 1.9% | 4% | ||||
80KVA | 180W | 1310/1250W | 1.9% | 4% | ||||
100KVA | 200W | 1580/1500W | 1.8% | 4% | ||||
125KVA | 240W | 1890/1800W | 1.7% | 4% | ||||
160KVA | 280W | 2310/2200W | 1.6% | 4% | ||||
200KVA | 340W | 2730/2600W | 1.5% | 4% | ||||
250KVA | 400W | 3200/3050W | 1.4% | 4% | ||||
315KVA | 480W | 3830/3650W | 1.4% | 4% | ||||
400KVA | 570W | 4520/4300W | 1.3% | 4% | ||||
500KVA | 680W | 5410/5150W | 1.2% | 4% | ||||
630KVA | 810W | 6200W | 1.1% | 4.5% | ||||
800KVA | 960W | 7500W | 1.0% | 4.5% | ||||
1000KVA | 1150W | 10300W | 1.0% | 4.5% | ||||
1250KVA | 1360W | 12000W | 0.9% | 4.5% | ||||
1600KVA | 1640W | 14500W | 0.8% | 4.5% | ||||
2000KVA | 1960W | 19800W | 0.8% | 5% | ||||
2500KVA | 2310W | 23000W | 0.7% | 5% |
Installation Instructions: Comprehensive guidance for a seamless and efficient installation process.
1. Installation Form: Choose the optimal installation method tailored to your environment.
Our 20kV oil-immersed transformers offer versatile installation options, including pole-mounted setups, robust outdoor installations, and secure indoor configurations.
For outdoor installations, secure the unit on a reinforced concrete foundation. Indoor setups require the transformer body to align flush with the cabinet front, ensuring a snug fit with the distribution panel.
2. Installation Steps: Follow our detailed steps for a flawless installation experience.
Utilize the specially designed force points for positioning the transformer and implement anti-slip measures to ensure stability.
During transportation and installation, control the transformer's inclination: no more than 15° along the long axis and 10° along the short axis to maintain optimal performance.
Ensure each component's gaps are neither too tight nor too loose for an impeccable installation.
Select appropriate insulation disks based on actual conditions and ensure correct wiring when installing terminals.
3. Attachment Installation: Secure accessory installations adhering to industry standards and manufacturer specifications.
Install accessories like gas relays, pressure relief devices, and moisture absorbers following relevant standards and manufacturer guidelines for optimal functionality.
Certificates: A testament to our commitment to quality, safety, and environmental stewardship.