Customization: | Available |
---|---|
Application: | Power, Instrument, Rectifier |
Phase: | Three |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Product Name: 10kv/20kv/35kv 0.4 Oil-Immersed Three-Phase Transformer
Experience the epitome of electrical engineering with our 20kV Oil-Immersed Transformer. This state-of-the-art equipment, ingeniously utilizing insulating oil as its medium, boasts an integrated design featuring a robust iron core, precision-engineered coils, a versatile voltage regulating switch, and a durable oil tank. Its primary function is to seamlessly alter voltage and facilitate the efficient transmission of alternating current energy. Distinguished by its compact dimensions, budget-friendly pricing, and exceptional weather resilience, this transformer is an invaluable asset across a myriad of industries including power systems, industrial operations, mining enterprises, transportation, postal services, telecommunications, and scientific research institutions.
nominal
capacity
|
high
voltage side
|
High voltage
tap range
|
low
voltage side
|
Connection
group labeling
|
No-
load loss
|
Load Loss |
No-load
current
|
Short Circuit
Impedance
|
30KVA |
11KV
10.5KV
10KV 6.3KV 6KV |
±5
±2×2.5%
|
0.4KV
0.69KV
|
Dyn11
Yyn0
|
100W | 630/600W | 2.3% | 4% |
50KVA | 130W | 910/870W | 2.0% | 4% | ||||
63KVA | 150W | 1090/1040W | 1.9% | 4% | ||||
80KVA | 180W | 1310/1250W | 1.9% | 4% | ||||
100KVA | 200W | 1580/1500W | 1.8% | 4% | ||||
125KVA | 240W | 1890/1800W | 1.7% | 4% | ||||
160KVA | 280W | 2310/2200W | 1.6% | 4% | ||||
200KVA | 340W | 2730/2600W | 1.5% | 4% | ||||
250KVA | 400W | 3200/3050W | 1.4% | 4% | ||||
315KVA | 480W | 3830/3650W | 1.4% | 4% | ||||
400KVA | 570W | 4520/4300W | 1.3% | 4% | ||||
500KVA | 680W | 5410/5150W | 1.2% | 4% | ||||
630KVA | 810W | 6200W | 1.1% | 4.5% | ||||
800KVA | 960W | 7500W | 1.0% | 4.5% | ||||
1000KVA | 1150W | 10300W | 1.0% | 4.5% | ||||
1250KVA | 1360W | 12000W | 0.9% | 4.5% | ||||
1600KVA | 1640W | 14500W | 0.8% | 4.5% | ||||
2000KVA | 1960W | 19800W | 0.8% | 5% | ||||
2500KVA | 2310W | 23000W | 0.7% | 5% |
Installation Instructions:
1. Installation Form:
Choose from versatile installation options for the 20kV oil-immersed transformers, including pole-mounted installations, robust outdoor setups, and efficient indoor transformer installations.
For outdoor installations, secure the transformer on a reinforced concrete foundation. Indoor installations require precise alignment, ensuring the transformer is flush with the cabinet front, impeccably integrated with the distribution panel, leaving no room for gaps.
2. Installation Steps:
Ensure placement precision by using designated force points, supplemented with anti-slip measures to enhance stability and safety.
Maintain optimal inclination control during transportation and installation, keeping it within the specified range: no more than 15° longitudinally and 10° transversely.
During setup, meticulous attention to part spacing is crucial to avoid excessive tightness or looseness.
Select appropriate insulation disks for terminal installations, aligning with the real-time conditions for accurate wiring.
3. Attachment Installation:
Adhere to strict standards and manufacturer's guidelines when installing accessories such as gas relays, pressure relief devices, moisture absorbers, and sleeves, ensuring seamless integration and functionality.
Certificates: