10kV/20kV/35kV 0.4 Oil-Immersed Three-Phase Transformer
Introducing the 20kV oil immersed transformer-an essential powerhouse in electrical equipment design, utilizing insulating oil as its medium. It comprises an iron core, coil, voltage regulating switch, and oil tank, designed to change voltage and transmit alternating current energy. This remarkable product stands out for its compact size, cost-efficiency, and robust weather resistance, making it the preferred choice across diverse sectors, including power systems, industrial and mining enterprises, transportation, postal and telecommunications departments, and scientific research institutions.
nominal
capacity
|
high
voltage side
|
High voltage
tap range
|
low
voltage side
|
Connection
group labeling
|
No-
load loss
|
Load Loss |
No-load
current
|
Short Circuit
Impedance
|
30KVA |
11KV
10.5KV
10KV 6.3KV 6KV |
±5
±2×2.5%
|
0.4KV
0.69KV
|
Dyn11
Yyn0
|
100W | 630/600W | 2.3% | 4% |
50KVA | 130W | 910/870W | 2.0% | 4% | ||||
63KVA | 150W | 1090/1040W | 1.9% | 4% | ||||
80KVA | 180W | 1310/1250W | 1.9% | 4% | ||||
100KVA | 200W | 1580/1500W | 1.8% | 4% | ||||
125KVA | 240W | 1890/1800W | 1.7% | 4% | ||||
160KVA | 280W | 2310/2200W | 1.6% | 4% | ||||
200KVA | 340W | 2730/2600W | 1.5% | 4% | ||||
250KVA | 400W | 3200/3050W | 1.4% | 4% | ||||
315KVA | 480W | 3830/3650W | 1.4% | 4% | ||||
400KVA | 570W | 4520/4300W | 1.3% | 4% | ||||
500KVA | 680W | 5410/5150W | 1.2% | 4% | ||||
630KVA | 810W | 6200W | 1.1% | 4.5% | ||||
800KVA | 960W | 7500W | 1.0% | 4.5% | ||||
1000KVA | 1150W | 10300W | 1.0% | 4.5% | ||||
1250KVA | 1360W | 12000W | 0.9% | 4.5% | ||||
1600KVA | 1640W | 14500W | 0.8% | 4.5% | ||||
2000KVA | 1960W | 19800W | 0.8% | 5% | ||||
2500KVA | 2310W | 23000W | 0.7% | 5% |
Installation Instructions:
1. Installation form:
Our 20kV oil immersed transformers offer a variety of installation forms, including pole-mounted, outdoor, and indoor transformer installations.
For outdoor installations, the transformer should be securely fixed on a reinforced concrete foundation. Indoor installations require the transformer to be flush with the cabinet's front, ensuring a snug fit against the distribution panel.
2. Installation steps:
When positioning the transformer, it is crucial to use the specially designed force points and implement anti-slip measures for safety.
During transport and installation, maintain the transformer's inclination within specified limits (no more than 15° along the long axis and 10° along the short axis) to ensure stability.
Ensure appropriate spacing between components during installation to prevent excessive tightness or looseness.
For terminal installations, select suitable insulation disks based on actual conditions and ensure proper wiring.
3. Attachment installation:
Accessories such as gas relays, pressure relief devices, desiccants, and sleeves should be installed in accordance with relevant standards and manufacturer guidelines to maintain product integrity.