10kv/20kv/35kv 0.4 Oil-Immersed Three-Phase Transformer
A 20kV oil immersed transformer serves as a vital electrical apparatus utilizing insulating oil as its medium. Comprising an iron core, coil, voltage regulating switch, and oil tank, this transformer is pivotal in altering voltage and enabling the transmission of alternating current. This product stands out for its compact size, affordability, and robust weather resistance, making it indispensable across power systems, industrial and mining sectors, transportation, postal and telecom departments, as well as in scientific research institutions.
nominal
capacity
|
high
voltage side
|
High voltage
tap range
|
low
voltage side
|
Connection
group labeling
|
No-
load loss
|
Load Loss |
No-load
current
|
Short Circuit
Impedance
|
30KVA |
11KV
10.5KV
10KV 6.3KV 6KV |
±5
±2×2.5%
|
0.4KV
0.69KV
|
Dyn11
Yyn0
|
100W | 630/600W | 2.3% | 4% |
50KVA | 130W | 910/870W | 2.0% | 4% | ||||
63KVA | 150W | 1090/1040W | 1.9% | 4% | ||||
80KVA | 180W | 1310/1250W | 1.9% | 4% | ||||
100KVA | 200W | 1580/1500W | 1.8% | 4% | ||||
125KVA | 240W | 1890/1800W | 1.7% | 4% | ||||
160KVA | 280W | 2310/2200W | 1.6% | 4% | ||||
200KVA | 340W | 2730/2600W | 1.5% | 4% | ||||
250KVA | 400W | 3200/3050W | 1.4% | 4% | ||||
315KVA | 480W | 3830/3650W | 1.4% | 4% | ||||
400KVA | 570W | 4520/4300W | 1.3% | 4% | ||||
500KVA | 680W | 5410/5150W | 1.2% | 4% | ||||
630KVA | 810W | 6200W | 1.1% | 4.5% | ||||
800KVA | 960W | 7500W | 1.0% | 4.5% | ||||
1000KVA | 1150W | 10300W | 1.0% | 4.5% | ||||
1250KVA | 1360W | 12000W | 0.9% | 4.5% | ||||
1600KVA | 1640W | 14500W | 0.8% | 4.5% | ||||
2000KVA | 1960W | 19800W | 0.8% | 5% | ||||
2500KVA | 2310W | 23000W | 0.7% | 5% |
Installation Instructions:
1. Installation form:
The versatile 20kV oil immersed transformers can be installed via pole-mounted setups, outdoor installations, or positioned indoors to suit various environmental conditions.
For outdoor installations, secure the transformer on a reinforced concrete foundation; whereas, indoor installations require the transformer to align precisely with the cabinet's front, ensuring a snug, gap-free fit against the distribution panel.
2. Installation steps:
Upon placement, employ specially designed force points to stabilize the transformer and implement anti-slip measures for maximum safety.
Maintain a controlled inclination during both transportation and installation, ensuring the long axis does not exceed a 15° tilt and the short axis remains within a 10° tilt.
Ensure proper spacing between components during installation to prevent overly tight or loose connections.
Install terminals using appropriate insulation disks tailored to the situation, with precise and correct wiring.
3. Attachment installation:
When fitting accessories such as gas relays, pressure relief devices, moisture absorbers, and sleeves, adhere strictly to relevant standards and manufacturer specifications.