10KV/20KV/35KV 0.4 Oil-Immersed Three-Phase Transformer
Behold the cutting-edge 10KV/20kV35KV oil-immersed transformer, an extraordinary marvel in electrical engineering. Employing insulating oil as its core medium, this transformer features an intricately designed iron core, precision-engineered coil, adaptable voltage regulating switch, and a robust oil tank. It serves as an indispensable tool for voltage transformation and seamless AC energy transmission. With its compact design, affordable pricing, and formidable weather resistance, this transformer is the favored choice across power systems, industrial and mining establishments, transportation, postal and telecommunications sectors, as well as research institutions.
nominal
capacity
|
high
voltage side
|
High voltage
tap range
|
low
voltage side
|
Connection
group labeling
|
No-
load loss
|
Load Loss |
No-load
current
|
Short Circuit
Impedance
|
30KVA |
11KV
10.5KV
10KV 6.3KV 6KV |
±5
±2×2.5%
|
0.4KV
0.69KV
|
Dyn11
Yyn0
|
100W | 630/600W | 2.3% | 4% |
50KVA | 130W | 910/870W | 2.0% | 4% | ||||
63KVA | 150W | 1090/1040W | 1.9% | 4% | ||||
80KVA | 180W | 1310/1250W | 1.9% | 4% | ||||
100KVA | 200W | 1580/1500W | 1.8% | 4% | ||||
125KVA | 240W | 1890/1800W | 1.7% | 4% | ||||
160KVA | 280W | 2310/2200W | 1.6% | 4% | ||||
200KVA | 340W | 2730/2600W | 1.5% | 4% | ||||
250KVA | 400W | 3200/3050W | 1.4% | 4% | ||||
315KVA | 480W | 3830/3650W | 1.4% | 4% | ||||
400KVA | 570W | 4520/4300W | 1.3% | 4% | ||||
500KVA | 680W | 5410/5150W | 1.2% | 4% | ||||
630KVA | 810W | 6200W | 1.1% | 4.5% | ||||
800KVA | 960W | 7500W | 1.0% | 4.5% | ||||
1000KVA | 1150W | 10300W | 1.0% | 4.5% | ||||
1250KVA | 1360W | 12000W | 0.9% | 4.5% | ||||
1600KVA | 1640W | 14500W | 0.8% | 4.5% | ||||
2000KVA | 1960W | 19800W | 0.8% | 5% | ||||
2500KVA | 2310W | 23000W | 0.7% | 5% |
Installation Instructions:
1. Installation form:
The versatile installation options for 20kV oil-immersed transformers include pole-mounted configurations, outdoor setups, and seamless indoor installations.
When opting for outdoor installations, secure the transformer on a reinforced concrete base; for indoor setups, ensure the transformer aligns precisely with the cabinet front, maintaining a snug fit against the distribution panel without any gaps.
2. Installation steps:
Upon positioning the transformer, utilize the designated special force points for stabilization, implementing anti-slip measures to secure it firmly in place.
During transportation and installation, maintain the transformer's inclination within safe limits; no more than 15° along the long axis and no more than 10° along the short axis.
Ensure optimal spacing between components during installation to prevent any excessive tightness or looseness.
Select and install the appropriate insulation disks for terminals, ensuring correct and secure wiring.
3. Attachment installation:
When installing additional components such as gas relays, pressure relief mechanisms, moisture absorbers, and sleeves, adhere to the relevant standards and manufacturer guidelines thoroughly.
Certificates: